压力传感器压力传感器安装位置加压后的风再分别通过每层的百叶窗或风阀送往每层的前室或楼梯间。当消防前室或楼梯间的通风压力或压差超过设定值(前室25~30Pa,楼梯间40-50Pa)时,电梯前室压力传感器安装位置,位于每层的压力传感器顺即时发出信号报警输入旁通泄压阀控制箱,旁通泄压阀控制箱根据压力传感器的信号打开旁通泄压阀,旁通泄压阀打开后,部分加压送风机送往风管的风通过旁路风管经过旁通泄压阀回到风机前端(红色箭头位置)
The compressed air is then sent to the front room or stairwell of each floor through the shutters or the air valve. When the ventilation pressure or pressure difference in the fire chamber or Stairwell exceeds the set value (25 ~ 30 PA in the Front Chamber and 40-50 PA in the Stairwell) , the pressure sensor located on each floor immediately sends a signal to the by-pass pressure relief valve control box, the by-pass Pressure Relief Valve control box opens the by-pass pressure relief valve according to the signal of the pressure sensor, part of the pressurized air supply fan to the air duct through the Bypass Air Duct by-pass Relief Valve back to the Fan Front (Red Arrow ition)
前室压力压力传感器压力传感器安装位置电梯前室压力传感器/防烟楼梯间差压控制控制器详解Technical Parameters: Measuring Range: 0 ~ 100PA PRESSURE: 1000PA Technical Parameters: Measuring Range: 0 ~ 100PA PRESSURE: 1000PA Action pressure: FRONT CHAMBER/AISLE: 25 ~ 30PA, (reset pressure: 15 ~ 20PA) ; Stairwell/front Chamber: 40 ~ 50PA, (reset pressure: 30 ~ 40PA) ; working temperature:-20 ~ 85 °C Action pressure: FRONT CHAMBER/AISLE: 25 ~ 30PA, (reset pressure: 15 ~ 20PA) ; Stairwell/front Chamber: 40 ~ 50PA, (reset pressure: 30 ~ 40PA) ; working temperature:-20 ~ 85 °C 电梯前室压力传感器/防烟楼梯间差压控制控制器详解
安装传感器的目的当火灾发生时,保持前室压差在25-30帕范围,前室风压力传感器,消防压力传感器安装位置,阻止有害烟气进入的同时,保证了防火门的正常开启。防止因前室的余压值过大,压力传感器安装位置,防火门无法开启,而造成严重后果,前室风压力传感器由我有限公司提供。我公司位于山东德州市鲁权屯千亩工业园。在市场经济的浪潮中拼博和发展,目前我公司空调在风机、排风设备中享有良好的声誉。我公司取得全网商盟认证,标志着我们的服务和管理水平达到了一个新的高度,欢迎新老客户来人参观指导。
紫旭空调没有中间商-消防楼梯间前室压力传感器安装位置由武城县豪鲁邦空调设备有限公司提供。紫旭空调没有中间商-消防楼梯间前室压力传感器安装位置是武城县豪鲁邦空调设备有限公司今年新升级推出的,以上图片仅供参考,请您拨打本页面或图片上的联系,索取联系人:危经理。