KFD2-SH-Ex1开关量安全栅,单通道,短路/断路检测功能,适用于传感器等。
• 1-channel isolated barrier
• 24 V DC supply (Power Rail)
• Input for approved dry contacts or SN/S1N sensors
• Relay output
• Fault indication output
• Line fault detection (LFD)
• Up to SIL3 acc. to IEC 61508
• Up to PL d acc. to EN ISO 13849
Function
This isolated barrier is used for intrinsic safety applications.
The device transfers digital signals (SN/S1N proximity
sensors or approved dry contacts) from a hazardous area to a
safe area.
The input controls one relay contact output with 3 NO contacts
(one output is in series to the both output relays for the safety
function), one relay contact output with one NO contact, and
one passive transistor output.
Unlike an SN/S1N series proximity sensor, a mechanical
contact, requires a 10 kΩ resistor to be placed across the
contact in addition to a 1.5 kΩ resistor in series.
Lead breakage (LB) and short circuit (SC) conditions of the
control circuit are continuously monitored.
During an fault condition, the fault indication output energizes
and outputs I and II de-energize.
For safety applications up to SIL3, output I must be used. For
safety applications up to SIL2, output I and output II can be
used.