赛特蓄电池BT-HSE-70-12 全系列产品简介
赛特蓄电池BT-HSE-70-12 全系列产品简介
赛特蓄电池BT-HSE-70-12 全系列产品简介
赛特蓄电池主要技术特点:
Main technical features of Saite battery:
1、不需维护:
1. No maintenance required:
电池在整个使用寿命期间无需加水补液。可靠性高、使用寿命长,特殊的密封结构和阻燃外壳,在使用过程中不会产生泄漏电解液的缺陷,更不会发生火灾。
There is no need to add water to the battery during the whole service life. High reliability, long service life, special sealing structure and flame-retardant shell, in the use process will not produce leakage of electrolyte defects, not to mention fire.
2、重量、体积比能量高,内阻小,输出功率高:
2. High specific energy of weight and volume, small internal resistance and high output power:
自放电小,20℃下每月的自放电率不大于2%。?满荷电出厂,无流动的电解液,运输安全。
The self discharge rate is less than 2% per month at 20 ℃. ? leave factory with full charge, no flowing electrolyte, safe transportation.
3、使用温度范围广:
3. Wide temperature range:
标准系列电池(-30℃~50℃),高温系列(-45℃~70℃)?无需均衡充电,由于单体电池的内阻、容量,浮充电压一致性优良,确保了电池在使用期?间,无需均衡充电。
Standard series batteries (- 30 ℃ ~ 50 ℃) and high temperature series (- 45 ℃ ~ 70 ℃)? Do not need to be charged evenly. Due to the internal resistance, capacity and good consistency of floating charge voltage of single battery, it is ensured that the battery does not need to be charged evenly during its service life.
4、恢复性能好:
4. Good recovery performance:
将电池过放电至0伏,短路放置30天后,仍可充电恢复其容量。坚固的铜??端子:便于安装连接,导电能力强。
When the battery is over discharged to 0 V and short circuited for 30 days, it can still be charged to restore its capacity. Solid copper? Terminal: easy to install and connect, strong conductivity.
赛特蓄电池主要应用领域:
Main application fields of Saite battery:
1、计算机辅助设计和计算机控制主要生产过程,确保产品性能的一致性并达到设计标准
1. Computer aided design and computer control the main production process to ensure the consistency of product performance and meet the design standards
2、应用太阳能光伏系统,路灯及城市亮化工程,风力发电储能,风光互补路灯,庭院灯,航标灯,信号灯,发电厂,变电站?,电信,通讯,电力,核电站,水电站。
2. Solar photovoltaic system, street lamp and urban lighting engineering, wind power generation and energy storage, landscape complementary street lamp, courtyard lamp, beacon lamp, signal lamp, power plant, substation, telecommunication, communication, power, nuclear power plant, hydropower station.
、UPS不间断电源,EPS应急电源,微波中继站,备用电源,所有直流电源、交流直流逆变系统,铁路机车车辆,电动车,船舶,电动游艇,电动船,交换机,应急照明,煤矿防爆牵引,电瓶车,叉车,汽车起动,照明,防火,警报,医疗,遥测设备,安全系统,手提式电源,可携式电动器具,泵系统等
3. UPS uninterruptible power supply, EPS emergency power supply, microwave relay station, standby power supply, all DC power supply, AC DC inverter system, railway rolling stock, electric vehicle, ship, electric yacht, electric ship, switch, emergency lighting, coal mine explosion-proof traction, battery car, forklift, car start, lighting, fire protection, alarm, medical, telemetry e, safety system, portable Type power supply, portable electric appliance, pump system, etc
备注:以上可以根据客户要求制作不同规格
Note: the above specifications can be made according to customer re
泉州赛特蓄电池BT-HSE-70-12南京代理价格
Saite battery bt-hse-70-12 Nanjing agency price
赛特蓄电池BT-HSE-70-12 全系列产品简介
HIFT UPS的冗余配置方案
现在的实际负载为25KW,由于HIFT UPS随需扩容的性能优势,可以按照现在的实际负载先进行配置,所以,负载容量按照25KW进行配置。
25KW/(0.8*0.8)≈40KVA,根据客户的需求,需要冗余并联方案。
2.2.2方案 2台HIFT 40KVA系统并联 总容量80KVA
2台40KVA系统并联,每台UPS 2个模块,共4个模块,总容量80KVA。系统正常运行时,每一个模块均分负载,现负载量为25KW,4个模块均分负载,每个模块6.4KW均流运行。
当市电正常的时候,如果其中任意一台模块出现故障,在系统控制程序命令下自动退出系统,其余模块将自动平均分担该故障模块所带的负载。
由于实际负载容量是25KVA,实际功率容量只占2台功率模块,而冗余2台功率模块,是2+2的系统。也就是说只有在3个模块同时故障的时候,UPS才会转旁路工作,才会在无保护的状态下运行。
在系统正常运行的情况下,市电发生故障(掉电或电压超限)时,两台UPS同时转到电池逆变运行,在此期间,如果其中一台模块发生故障,该故障模块脱出系统,其余模块均分该故障模块负载后,继续正常电池逆变运行。
随着客户负载的增长,可随时在线添加功率模块,(每个模块20KVA),大可扩容到240KVA,已经远远超过客户对今后的扩容要求。
2.2.3普通UPS 1+1冗余并机系统与HIFT UPS方案配置比较
2.2.3.1 可靠性比较
在本案例中,普通UPS 1+1并联冗余系统的可靠性计算公式如下:
公式中:
R:表示系统可靠性
F(t):故障概率
如果单机可靠性为R(t)=0.99,代入公式得出1+1并联系统的可靠度为:R (1+1)=0.9999
HIFT UPS在方案1中,也采用主机40KVA 系统并联冗余,但由于其模块化结构设计,可组成N+X并联系统,也就是在系统冗余的情况下在冗余,组成2+2系统,依据系统的可靠性模型,计算如下 :
其中m=2 ,n=2 计算得出 R(2+2)=0.999996
系统方案可靠度比较
通过以上对普通UPS 1+1并联与HIFT UPS N+X冗余方案可靠性分析和比较,可以得出以下的结论:
由单机1+1组成冗余供电系统,当单机可靠度为0.99时,并机系统可靠度可达到0.9999。
由HIFT UPS组成的1+1冗余系统中,当单个模块同样可靠度同样为0.99时,双系统并联组成的2+2系统的可靠度为0.,比1+1系统的可靠度高出20万倍。
另外,由单机1+1组成冗余供电系统,当单机可靠度为0.99时,并机系统可靠度达到0.9999,此值与负载量无关,也就是说,不管系统实际负载量是多少,系统永远是1+1冗余,不允许两台同时故障,可靠度永远是0.9999;
但是在HIFT UPS组成的N+X冗余供电系统,系统的实际负载量占设备容量的大小与系统的可靠度息息相关,实际负载量越低,系统可靠度越高。客户可以通过在线增加功率模块来提高系统可靠度。以保证系统安全运行。
2.2.3.2 经济性比较
(1)设备购置成本